Eagle Security Means Quality
Eagle Security Offers the Best in Security Options

design_flow.jpg (19423 bytes)
Fire and Waterflow

(Future) Download ADEMCO Security System control panels with Compass The 5110XM
Fire Alarm Communicator for Waterflow Supervision
5110XM Control PRIMARY FEATURES:
UL 864 listed commercial fire
NFPA 72 central station and remote station compliance
Sprinkler supervision or slave applications
5 supervised style B initiating circuits
1 notification appliance circuit
Downloadable - standard
Dual phone line - standard
24 hour test
Major communications formats
TO: System Description Expanded Features Built-in Indicators & Switches
Relay Outputs Remote Keypads Communication Programming Regulatory Agency Listing Dimensions Electrical Specifications Communications Format
SYSTEM DESCRIPTION
The ADEMCO 5110XM is a 5 zone fire control communicator. It is designed specifically to offer digital fire reporting over the dial-up telephone network.

The model 5110XM is approved for use in applications required to meet UL 864 and NFPA 72 requirements. These requirements include the monitoring of local evacuation controls. The 5110XM will monitor dry contact alarm and trouble outputs and transmit a separate code for each. The 5110XM can be used as a stand-alone to monitor sprinkler systems for waterflow, supervisory and gate valve tamper conditions. The unit is fully supervised and supports one two-wire smoke detection circuit. Its microprocessor constantly runs programs to monitor AC, standby battery, zone inputs and the telephone line connections. If a fault condition is detected, it sounds a local trouble audible and reports the condition to the central station. If one of the telephone lines faults, it will automatically switch to the other to report the failure.

The 5110XM conducts an automatic self-test every 24 hours - at a time you select - and sends a report to the central station.

EXPANDED FEATURES
Zones Supported

  • Up to 5 Style B hardwired zones
  • Each zone programmable for:

- fire alarm without verification
- 24-hour non-fire
- audible or silent alarm
- fire alarm with verification
- fire waterflow alarm
- fire sprinkler supervisory

BUILT-IN INDICATORS & SWITCHES

  • Warning buzzer
  • Seven LED indictors for:

    - AC trouble
    - silenced audible conditions
    - battery trouble
    - telco line fault
    - telco line seizure
    - communications failure
    - silenced/reset push-button switch which allows audibles to be silenced and smoke detectors to be reset

RELAY OUTPUTS

  • Style Y EOL supervised indicating circuit
  • Auxiliary relay Form C output

REMOTE KEYPADS

  • 6137R (red) fixed word keypads
  • 6139R (red) alpha keypads

COMMUNICATION
Main and back-up telephone interfaces which allow alarm, supervisory and trouble conditions to be reported to central station.

PROGRAMMING
May be programmed on-site using the 6139/6139R alpha keypads or remotely via telephone lines using IBM compatible PC running ADEMCO V-LINK download software and Hayes modem.

REGULATORY AGENCY LISTING
UL 864/NFPA 72 commercial fire, central station and remote station

DIMENSIONS
5110XM Communicator Physical: 14-1/2" H x 12-1/2" W x 3" D

ELECTRICAL SPECIFICATIONS
AC
POWER
Built-in AC power transformer which requires nominal 120VAC, 600mA input

BATTERY
12VDC, 7AH min-14AH max lead acid battery float charging voltage: 13.7VDC nominal 24 hours standby time with up to 350mA combined aux. power/aux. relay load using 14AH battery 60 hour standby time with up to 55mA combined aux. power/aux. relay load using 14AH battery.

OUTPUT POWER
Combined auxiliary power and auxiliary relay standby currents cannot exceed 350mA combined auxiliary power, auxiliary relay and bell alarm currents cannot exceed 1A.

COMMUNICATIONS FORMATS
ADEMCO, Sescoa, Radionics 3+1/4+1/4+2 low speed, ADEMCO Express,
ADEMCO Contact ID.