SYSTEM
DESCRIPTION
The 5120XM is a UL Listed, microprocessor based 5-zone commercial fire and burglary
control communicator. It can monitor fire alarm, emergency alarm, burglary alarm and fire
sprinkler supervisory sensors. When the 5120XM detects an alarm, supervisory or trouble
condition, it triggers an on-premises warning indication and transmits a message to a
central station via the dial-up telephone network. The 5120XM is UL864 listed and
conforms to NFPA72 standards for local, central station and remote station services. Five
supervised style B initiating circuits are provided and each circuit is programmable for a
full range of responses.
Two telephone lines are supervised. Audible signal circuits are 24VDC, 1.7A power,
suitable for ADA compliant strobes, 24V indicating circuit and an auxiliary form C relay.
The 5120XM supports one two-wire smoke detection circuit.
The 5120XM sends a test signal to the central station every 24 hours.
EXPANDED FEATURES
Zones Supported
RELAY OUTPUTS
- 12V, 1A style Y EOLR Style supervised indicating circuit for polarized 24V fire alarm
- Auxiliary relay Form C output
REMOTE KEYPADS
- 6137R fixed word keypads or 6139R alpha keypads
COMMUNICATION
Main and back-up telephone interfaces which allow alarm, supervisory and trouble
conditions to be reported to central station.
PROGRAMMING
May be programmed on-site using the 6139/6139R alpha keypads
or remotely via telephone lines using IBM compatible PC running ADEMCO V-LINK download
software and Hayes modem.
REGULATORY AGENCY
LISTING
- UL 864/NFPA 72 Local, central station and remote station fire alarm service
- UL 609 Grade A Local Mercantile Premises and Local Mercantile Safe and Vault burglary
alarm service
- UL 611/UL 1610 Grade B Central Station burglary alarm service (Grade A service will be
available with the future 7720PLUS LORRA)
- UL 365 Grade A Police Connect burglary alarm service
DIMENSIONS
5120XM Communicator Physical: 18" H x 14.5" W x 4.3" D
ELECTRICAL SPECIFICATIONS
AC POWER
Built-in AC power transformer which supports the 5120XM (and PS24 power supply module) and
requires nominal 120VAC, 2.5A input
BATTERY
12VDC, 7AH min-24AH max lead acid battery Float charging voltage; 13.7VDC nominal when
5120XM without PS24 power supply; 24 hour standby time with up to 400mA combined aux
power, #1/aux power, #2/aux relay load using 24AH battery. 60 hour standby time with up to
225mA combined aux power #1/aux power #2/aux relay load using 24 AH battery
OUTPUT POWER
Combined auxiliary power #1, auxiliary power #2 and auxiliary relay standby currents
cannot exceed 400mA. Combined auxiliary relay power #1, auxiliary #2, auxiliary relay and
bell alarm currents cannot exceed 1A
COMMUNICATIONS FORMATS
ADEMCO, Sescoa, Radionics 3+1/4+1/4+2 low speed, ADEMCO Express, ADEMCO Contact ID. |